Briggs & Stratton 100kW Standby Generator – 277/480V Three-Phase Backup Power
The Briggs & Stratton 100kW Standby Generator (Model 080013) delivers enterprise-grade three-phase backup power for warehouses, manufacturing plants, industrial facilities, and large commercial operations running on 277/480V Wye-configured electrical systems. When the grid fails, this unit restores three-phase power within seconds — keeping industrial motors, HVAC systems, compressors, commercial lighting grids, production equipment, and mission-critical infrastructure running without interruption.
Powered by a liquid-cooled, turbocharged PSI 5.7L V-8 engine producing 163 gross horsepower at a steady 1,800 RPM, this generator delivers 100kW of reliable three-phase output on either liquid propane vapor (LPV) or natural gas (NG) — giving you complete fuel flexibility at installation without hardware changes.
DSE 7310 Mk II Smart Controller
The integrated DSE 7310 Mk II controller provides web-based monitoring, RS232/RS485 remote communications, configurable I/O, a 250-event log, load switching, load shedding, integral PLC editor, runtime scheduling, and full power monitoring (kW, kVA, kVAR) — giving facility managers and electrical contractors complete operational visibility and control from on-site or remotely.
Block Heater & Battery Charger Included
Both accessories come standard. The block heater maintains engine temperature for reliable cold-weather starts, while the Marinco 6-amp battery charger keeps the 630 CCA starting battery at peak charge — ensuring the system is always primed and ready when you need it most.
Key Specifications
| Spec |
Detail |
| Standby Rating |
100 kW / 125 kVA @ 0.8 pf |
| Voltage |
277/480V, 3-Phase (Wye), 60 Hz |
| Breaker |
175A |
| Running Amperage |
150A |
| Engine |
PSI 5.7L V-8, Turbocharged, 1,800 RPM |
| Displacement |
5.7L / 350 ci |
| Compression Ratio |
9.4:1 |
| Rated Horsepower |
163 gross hp |
| Governor Type |
Electronic, Isochronous |
| Frequency Regulation |
Steady State ±0.5% |
| Ignition System |
HVS Distributor |
| Fuel Type |
LP Vapor / Natural Gas (Dual Fuel) |
| Fuel Supply Line Inlet |
1-1/4" NPT |
| Fuel Supply Pressure |
7–11 in H₂O / 17–28 mbar |
| Full-Load Fuel Use (NG) |
1,470 ft³/hr (41.7 m³/hr) |
| Half-Load Fuel Use (NG) |
893 ft³/hr (25.3 m³/hr) |
| No-Load Fuel Use (NG) |
311 ft³/hr (8.9 m³/hr) |
| Full-Load Fuel Use (LPV) |
585 ft³/hr (16.6 m³/hr) |
| Half-Load Fuel Use (LPV) |
334 ft³/hr (9.5 m³/hr) |
| No-Load Fuel Use (LPV) |
113 ft³/hr (3.2 m³/hr) |
| Sound Level |
81 dB(A) @ 7m, no-load |
| Alternator |
MeccAlte ECP34-1L/4, Brushless 12-Lead |
| Alternator Configuration |
Wye |
| THD |
< 3.5% |
| Voltage Regulation |
±1.0% NL to FL |
| One-Step Load Acceptance |
100% of Rating |
| Sustained Short-Circuit Current |
300% of Rated Current for 20 Seconds |
| Oil Capacity |
4.7L / 5.0 qt |
| Coolant Capacity (Total) |
34.2L / 36.1 qt |
| Battery |
12V, 630 CCA |
| Dimensions (L×W×H) |
120 × 52 × 86 in / 3048 × 1321 × 2184 mm |
| Weight |
4,125 lb / 1,871 kg |
| Enclosure |
Steel, Sound-Attenuated |
| Certifications |
UL, cUL |
| Warranty |
3-Year Parts, Labor & Travel |
175A Breaker for High-Voltage Three-Phase Industrial Loads
The factory-installed 175A breaker provides robust overload protection and simplified connection to your 277/480V three-phase Wye distribution panel. While the amperage is lower than the 120/208V and 120/240V variants, the higher voltage delivers the same 100kW output — making this configuration the standard choice for industrial facilities, warehouses, farms, and large commercial operations where 277/480V three-phase power is the established infrastructure standard.
The 277/480V Wye configuration supports industrial motors, high-voltage lighting systems, large HVAC equipment, compressors, and other heavy three-phase loads common in manufacturing and industrial environments. The sound-attenuated steel enclosure protects internal components from rain, wind, and harsh outdoor environments, while integral vibration isolation ensures smooth, stable operation. Optional accessories include liquid propane vaporizer kits, remote annunciator kits (DSE 2548-01), remote display modules (DSE 2510-32), emergency stop switches (NEMA 4X), communication interface module (DSE 890-01), AVR communication cable, battery warmer, and battery cable lockout for full installation flexibility.
Model: 080013
Warranty: 3-Year Parts, Labor & Travel
FAQ
What can the Briggs & Stratton 100kW 080013 generator power?
With 100kW / 150A of three-phase output at 277/480V Wye, this generator is sized for industrial facilities, warehouses, manufacturing plants, and large commercial operations. It simultaneously powers industrial motors, compressors, large HVAC systems, high-voltage lighting grids, production equipment, and other critical three-phase loads during an outage.
Why choose the 277/480V 080013 over the 120/208V 080011 or 120/240V 080012?
All three models deliver the same 100kW output on the same 5.7L V-8 engine platform. The 080013 is the right choice for facilities with existing 277/480V three-phase Wye infrastructure — the standard voltage for most industrial and heavy commercial environments. The 080011 suits office buildings and light commercial facilities on 120/208V Wye, and the 080012 serves facilities on 120/240V three-phase systems. Always confirm your facility's electrical configuration with a licensed electrician before ordering.
What fuel types does the 080013 support?
This generator is dual-fuel capable, running on either liquid propane vapor (LPV) or natural gas (NG). The fuel supply line inlet is 1-1/4" NPT and requires a supply pressure of 7–11 in H₂O (17–28 mbar). Full-load NG consumption is approximately 1,470 ft³/hr; LPV full-load consumption is approximately 585 ft³/hr. A liquid propane vaporizer kit is available as an optional accessory.
Does the Briggs & Stratton 080013 include an automatic transfer switch?
An automatic transfer switch (ATS) is not included but is available separately. When paired with a compatible ATS, this generator activates automatically within seconds of detecting a utility power failure — with no manual intervention required.
What does the 3-year warranty cover?
The Briggs & Stratton 3-year limited warranty covers parts, labor, and travel for domestic installations. The engine carries the same 3-year coverage. Enclosure surface rust and corrosion are covered for 1 year; rust-through is covered for 2 years. See the operator's manual or BRIGGSandSTRATTON.com for complete warranty terms.