Daikin Mini Split Error Codes: Full Chart and Fixes

Brian Schaeffer |

Quick answer: When a Daikin mini split stops and its operation lamp blinks, the unit has stored a malfunction code. On most Daikin wireless remotes, point the remote at the indoor unit and hold TIMER CANCEL for about 5 seconds until "00" shows, then press it repeatedly until you hear a long beep. The code on the display when you hear the long beep is the error. U4 (indoor/outdoor communication), A5 (freeze or high-pressure protection) and E7 (outdoor fan) are among the most common.

How to Read a Daikin Mini Split Error Code With the Remote

  1. Point the wireless remote at the indoor unit.
  2. Hold the TIMER CANCEL button for about 5 seconds. "00" flashes in the temperature display.
  3. Press TIMER CANCEL again, one press at a time. The display steps through possible codes.
  4. Listen to the indoor unit. One short beep or two short beeps mean the displayed code is not the stored one. One long beep means that code is the stored error. Write it down.
  5. To return to normal, hold TIMER CANCEL for 5 seconds. The display also clears itself if no button is pressed for 1 minute.

Some Daikin remotes use a different method: press TEMP up, TEMP down and MODE together to enter diagnosis mode, then change each digit until you hear a long beep. If your remote doesn't respond to TIMER CANCEL, check the operation manual for your model. A blinking operation lamp with no stored code can also be a normal protection state, so read the code before assuming a fault.

Daikin Mini Split Error Code Chart

Codes and descriptions below follow Daikin's service code list. Not every code applies to every model, so confirm with your unit's manual.

Code Daikin description What you can check
00 Normal, no stored error No action needed
A1 Malfunction of indoor unit PCB Call a technician
A3 Drain level control system abnormality Check the condensate drain for clogs or kinks; then call a technician
A5 High pressure control in heating, freeze-up protection control in cooling Clean the air filter and clear blocked airflow; call if it repeats
A6 Malfunction of fan motor (indoor) Call a technician
C4 Malfunction of liquid pipe thermistor for heat exchanger Call a technician (sensor)
C7 Front panel driving motor fault Call a technician
C9 Malfunction of suction air thermistor Call a technician (sensor)
E1 Defective outdoor unit PCB Call a technician
E5 Inverter compressor motor or overheat Turn the system off and call a technician
E6 Compressor motor overcurrent or lock Turn the system off and call a technician
E7 Malfunction of outdoor unit fan motor system Check that nothing blocks the outdoor fan; then call
E8 Overcurrent of inverter compressor Turn the system off and call a technician
EA Malfunction of four-way valve or cool/heat switching Call a technician
F3 Malfunction of discharge pipe temperature Turn the system off and call a technician
F6 Abnormal high pressure or refrigerant overcharged Check for a blocked outdoor coil; then call
H0 Malfunction of sensor system of compressor Call a technician
H6 Malfunction of position detection sensor Call a technician
H8 Malfunction of compressor input (CT) system Call a technician
H9 Malfunction of outdoor air thermistor Call a technician (sensor)
J3 Malfunction of discharge pipe thermistor Call a technician (sensor)
J6 Malfunction of heat exchanger thermistor (outdoor) Call a technician (sensor)
L3 Electrical component box temperature rise Check outdoor unit airflow; then call
L4 Inverter radiation fin temperature rise Check outdoor unit airflow; then call
L5 Inverter instantaneous overcurrent (DC output) Turn the system off and call a technician
P4 Malfunction of radiation fin temperature sensor Call a technician (sensor)
U0 Shortage of refrigerant Call a technician; this usually means a leak
U2 Malfunction of power supply or instantaneous power failure Check the breaker and incoming voltage
U4 Malfunction of transmission between indoor and outdoor unit Check the outdoor unit breaker, then power-cycle once
UA Improper combination of indoor and outdoor units Confirm the indoor and outdoor units are a Daikin-approved match
UH Malfunction of system Call a technician

The Most Common Daikin Codes, Explained

U4: Indoor and outdoor units aren't communicating

U4 means the indoor and outdoor units have lost their signal connection. Check that the outdoor unit's breaker or disconnect is on, then turn the system off at the breaker for a few minutes and restore power once. If U4 returns, a technician should check the connecting wiring, voltage and control boards.

A5: Freeze protection or high-pressure protection

A5 shows up when the indoor coil gets too cold in cooling or too hot in heating. The most common cause is restricted airflow, so clean the filter and make sure nothing blocks the indoor unit. If it repeats with a clean filter, call a technician.

U0: Refrigerant shortage

U0 points to low refrigerant, which almost always means a leak. Topping off refrigerant without finding the leak won't fix it. A licensed technician needs to find and repair the leak.

E5, E6, E8, F3 and L5: Compressor protection

These codes protect the compressor. Don't keep resetting the system to clear them. Turn it off and have a technician check it, since repeated restarts can damage the compressor.

Before You Call a Technician

  • Clean or replace the indoor unit's air filter.
  • Make sure nothing blocks the indoor unit or the outdoor coil and fan.
  • Check the breaker and outdoor disconnect.
  • Write down the code, model numbers and when the problem started.
  • Check your warranty status. Daikin's parts warranty depends on registration within 60 days of installation. See our Daikin mini split warranty guide.

FAQs

Why is my Daikin mini split blinking green?

A blinking operation lamp usually means the unit has stopped because of a malfunction and stored a code. Use the TIMER CANCEL method above to read it. Lamp colors vary by model.

How do I reset a Daikin mini split error?

For codes like U4 or U2, turn the system off at the breaker for a few minutes and restore power once. Don't keep resetting compressor-protection codes such as E5, F3 or L5.